Daikin Air Conditioning

<< Click to Display Table of Contents >>

Navigation:  Components > Manufacturer specific drivers >

Daikin Air Conditioning

This invisible driver component is intended for connection to "Daikin air conditioners". Depending on the device, individual data points cannot be used.

 

Global data points of the component

Name

Type

Function

Diagnosis [Text]

Output

Error texts are output here. These can be displayed e.g. with the component "Protocol window". Attention: Diagnosis or debug outputs are only provided for the case of an error. Please use only after consultation with the support team! If used, these can considerably impair the performance of the service

Extended diagnosis

Input

(De)Enables the extended debug output. Attention: Diagnosis or Debug - outputs are only provided for the case of error. Please use only after consultation with the support team! If used, these can significantly affect the performance of the service

Driver On/Off

Bidirectional

(De)Activating the component

Connection status

Output

Shows whether the connection to the device exists (true) or not (false).

 

 

Data points of the Daikin air conditioning systems

Name

Type

Function

Fan movement

Bidirectional

The fan movement can be controlled either directly via an on/off signal or via an input at the corresponding data point:

0 = Off

1 = Vertical fan movement

2 = Horizontal fan movement

3 = Horizontal and vertical fan movement

Fan rate

Bidirectional

The fan rate can be controlled either directly via an on/off signal or via an input at the corresponding data point:

A = car

B = Silent mode (Not supported by Daikin Emura FVXS)

3 = Level 1

4 = Level 2

5 = Level 3

6 = Level 4

7 = Level 5

Mode

Bidirectional

The mode can be controlled either directly by an on/off signal or by an input at the corresponding data point:

0 = Auto (temperature range 18-31°C)

1 = Auto (temperature range 18-31°C)

2 = Dehumidify

3 = Cold (temperature range 18-33°C)

4 = Hot (temperature range 10-31°C)

6 = Ventilation

7 = Auto (temperature range 18-31°C)

Power

Bidirectional

This can be used to switch the air conditioning on and off

Target Humidity

Bidirectional

Possibility to set the target humidity for the current mode (not supported by FTXG-L and FVXS).

Target temperature

Bidirectional

Depending on the mode, the target temperature can be set here. The input range is between 10 and 41°C.

 

 

Properties of the component

Name

Standard

Function

IP address

 

Enter the IP address of the Daikin air conditioner.

Status Check Interval [s]

1800

Setting for the update time in seconds.

Driver On/Off

 

(De)Activate the component.

 

Compatible devices:

wireless adapters

device name

device series

BRP069B42

Urura Sarara

FTXZ-N

BRP084A42-1

Stylish

CTXA-A*; FTXA-A*; FTXA-B*

BRP069B41

Emura

FTXJ-M*

BRP069B41

Perfera

CTXM-N; FTXM-N

BRP069B45

Comfora

FTXP-M

BRP069B45

Sensira (Austria)

FTXF-A

BRP069B45

Siesta (Germany)

ATXF-A