The maximum guard is an invisible server component with the possibility to realise load optimisation or load shedding. A more detailed description can be found under Functional Description.
If this component is created, it counts as 500 components.
One or more Maximum Monitor displays can be connected as a visible client component to display and operate the Maximum Monitor.
Data points of the component
Name |
Type |
function |
|---|---|---|
Dynamic |
Folder |
The data points for the defined channels are displayed in the Dynamic folder. These must be linked here. Each channel has a data pointoutput for the circuit, a data pointinput for blocking the circuit and an input for emergency shutdown of the channel. |
Settings |
Folder |
Contains data points for changes to the settings at runtime. (see below) |
Configuration by E-Mail |
Input |
This input of the maximum monitor receives new configuration data as a file attachment from the e-mailer. |
Cumulated power [kW] |
Output |
Cumulated power as float in kW. |
Lifecheck signal |
Output |
Life check signal which is sent every second. Can be used for monitoring. |
MAX 2 value change over |
Input |
If an on signal is applied to this input, it is switched to the power setpoint Max 2. (Low tariff) |
MAX 3 value change over |
Input |
If an ON signal is applied to this input, it is switched to the power setpoint Max 3. (Special tariff) |
MAX 4 value change over |
Input |
If an ON signal is applied to this input, it is switched to the power setpoint Max 4. (Special tariff) |
MaximumMonitor Display |
Bidirectional |
Link to one or multiple Maximum Monitor Display. |
Maximum Pre warning |
Output |
Will be set in case of a predicted power overstepping from the Maximumwarning system. |
Current power [kW] |
Output |
Momentary power as float in kW. |
Information [Text] |
Output |
Internal state information will be sent as string on this data point. For example the state information can be send to the E-Mailer component which can send a e-mail in case of power overstepping. |
Emergency mode |
Bidirectional |
This data point indicates the internal state of the "Maximum Monitor". In case of "on" the component is in emergency mode. In case of "off" the component is in normal mode. Furthermore the emergency mode can be triggered external with this data point by sending "on" value to this data point. |
Period power [kW] |
Output |
Current period power as float in kW. |
Trend power [kW] |
Output |
Current trend power as float in kW. |
Available period power [kW] |
Output |
Indicates the remaining period power for the period in kW. |
Counter working impulse |
Input |
This data point receives power values, energy values or energy impulses depending on the operating mode. |
Counter Synchronic impulse |
Input |
Synchronic impulse input from the energy supplier for the synchronisation of the measure period. |
Data points from the Settings folder
Name |
Type |
Function |
|---|---|---|
Calculation Hysteresis |
Bidirectional |
Input/output of the calculation hysteresis in %. |
Calculation interval |
Bidirectional |
Input/output of the calculation interval in seconds. |
Device parameters changed by e-mail |
Output |
This output gives an on signal when the maximum guard has received new device parameters by e-mail and these have been successfully accepted. |
Channel list changed by e-mail |
Output |
This output emits an ON signal when the maximum monitor has received new channel data by e-mail and these have been successfully accepted. |
Configuration by e-mail |
Input |
Via this input, the maximum controller receives new configuration data as a file attachment [text] (.txt) from the e-mailer. |
Max 1 Setpoint |
Bidirectional |
Input/output of the maximum setpoint for the stage in kW. |
Max 2 setpoint |
Bidirectional |
Input/output of the maximum setpoint for the step in kW. |
Max 3 setpoint |
Bidirectional |
Input/output of the maximum setpoint for the step in kW. |
Max 4 setpoint |
Bidirectional |
Input/output of the maximum setpoint for the step in kW. |
Properties
Name |
|
function |
|---|---|---|
Channel List |
|
Here the individual channels (switching stages) of the maximum guard and their parameters are defined. These then appear as channels in the data point Folder Dynamic. Details can be found in the following chapter Switch Channels. |
Device Parameter |
|
Here the general parameters for the maximum guard are set. Details can be found in the following chapter Device parameters. |