DLM distribution data

<< Click to Display Table of Contents >>

Navigation:  Components > E-Mobility >

DLM distribution data

This component is used to be able to connect several DLM v2 drivers in order to facilitate an output of the information of the distributions. The data at the outputs refers to the entire distribution in which the station is located, which is called up via "Station name".

 

 

Data points of the component

Name

Type

Function

Activated

Output

Indicates whether the driver is active (on) or not (off).

Number of charging points (incl. sub-distributions)

Output

Shows the number of charging points that are in the "Charging" state.

Number of charging points

Output

Outputs the number of charging points that are in the "Charging" state.

Diagnosis [Text]

Output

Attention: Diagnostic or debug outputs are only intended for use in the event of an error. Please use only after consultation with the support team! If used, they can significantly affect the performance of the service.

Extended Diagnosis

Input

(De)activate advanced diagnostics.

At least one charging point charges (incl. sub-distribution boards)

Output

Is set to "ON" if any connected charging point is in the "charging" state.

At least one charging point is charging (local)

Output

Is set to "ON" if any connected charging point is in the "charging" state.

Lock

Bidirectional

Option to block a specific sub-distribution. The distribution data is then no longer taken into account.

Current from supply line (L1)

Output

Output for the current from the supply line of the sub-distribution.

Current from supply line (L2)

Output

Output for the current from the supply line of the sub-distribution.

Current from supply line (L3)

Output

Output for the current from the supply line of the sub-distribution.

Current building (L1)

Output

Output for the current used by other consumers (without charging currents) of the distribution.

Current building (L2)

Output

Output for the current used by other consumers (without charging currents) of the distribution.

Current building (L3)

Output

Output for the current used by other consumers (without charging currents) of the distribution.

Measured current (L1)

Output

Output for the measured current on the input side of the distribution.

Measured current (L2)

Output

Output for the measured current upstream of the distribution.

Current measured (L3)

Output

Output for the measured current upstream of the distribution.

Total current (L1)

Output

Output for the current of the sub-distribution including other current sources such as PV system.

Total current (L2)

Output

Output for the current of the sub-distribution including further current sources, e.g. PV system.

Total current (L3)

Output

Output for the current of the sub-distribution including further current sources, e.g. PV system.

Current of charging stations (L1)

Output

Output for the measured current of the station.

Charging station current (L2)

Output

Output for the measured current of the station.

Charging station current (L3)

Output

Output for the measured current of the station.

Current maximum

Bidirectional

Output or change possibility of the maximum current of the distribution.

Current minimum

Bidirectional

Output or modification possibility of the minimum current of the distribution system

Current not used (referred to maximum)

Output

Outputs the current that is not used. This refers to the maximum current available for the distribution.

Current not used (referred to maximum) (L1)

Output

Outputs the current that is not used. This refers to the maximum current on L1 that is available for distribution.

Current not used (referred to maximum) (L2)

Output

Outputs the current that is not used. This refers to the maximum current on L2 that is available for distribution.

Current not used (referred to maximum) (L3)

Output

Outputs the current that is not used. This refers to the maximum current on L3 that is available for distribution.

Current not used (related to allocated current)

Output

Outputs the current that is not used by the charging point. It is the difference between the allocated and used current at the charging point.

Current not used (related to allocated current) (L1)

Output

Outputs the current on L1 that is not used by the charge point. It is the difference between the allocated and used current at the charging point.

Current not used (related to allocated current) (L2)

Output

Outputs the current on L2 that is not used by the charge point. It is the difference between the allocated and used current at the charging point.

Current not used (related to allocated current) (L3)

Output

Outputs the current on L3 that is not used by the charge point. It is the difference between the allocated and used current at the charging point.

Current Reserve

Bidirectional

Output or change possibility of the current reserve that is not distributed to the charging points.

Current used (max)

Output

Output of the maximum current used by one of the 3 phases.

Current assigned

Output

Output of the allocated maximum current of the distribution that can be distributed to the charging points.

Driver On/Off

Bidirectional

Driver On or Off.

Distribution Data (DLM)

Bidirectional

Connection to the DLM data point with the same name.

Distribution name

Bidirectional

A character string can be used to select the connected charging stations and output their information.

 

 

Properties of the component

Name

Standard

Function

Distribution name

 

Charging station name

Driver On/Off

 

Defines whether the driver is automatically activated at the start of the project.