<< Click to Display Table of Contents >> Navigation: Components > Manufacturer specific drivers > Assa Abloy FT-Connect |
This driver can be used to integrate the FT-Connect security and access control system.
Data points of the component
Component name |
Type |
Type Function |
|---|---|---|
Dynamic |
Folder |
Contains the data points created under "Channels". |
Diagnosis [Text] |
Output |
Error texts are output here. These can be displayed using the"Log window" component, for example. Attention: Diagnostic or debug outputs are only intended for errors. Please only use them after consulting the support team! If used, they can significantly impair the performance of the service |
Extended diagnostics |
Input |
(De)Activates the extended debug output. Attention: Diagnostic or debug outputs are only intended for use in the event of an error. Please only use them after consulting the support team! If used, they can significantly impair the performance of the service |
Messages [Text] |
Output |
Output of communication messages in text form. |
Driver On/Off |
Bidirectional |
(De)activation of the component at service start. |
Connection status |
Output |
If there is a connection to the device, an On signal is output. If the connection is interrupted, an Off signal is output (after the set time-out time). |
Properties of the component
Component name |
Standard |
Standard Function |
|---|---|---|
Connection |
|
Connection settings to the gateway with IP and login data. Only FTCUser1 or FTCUser2 can be used as the user. There are 2 IP ports, which are preset to 1100. The port (remote) is used for access from the EisBaer to the Assa Abloy FT-Connect (outgoing connection). The port (local) is used for the connection from the Assa Abloy FT-Connect to the EisBaer (incoming connection). Depending on the network, the firewall rules may need to be adjusted. |
Channels |
0 |
The devices are imported from the server and displayed in the channel list. The names must be unique. |
Update pause [s] |
5 |
Pause time between 2 system queries. |
Driver On/Off |
|
(De)Activation of the component at service start. |
Access only works with FTCUsers
A password must be set for these. To do this, the FT-Manager is called up with a web browser via the IP address. (Factory setting: https:\\1.1.1.1)
1.To activate the corresponding function (extended view), switch off automatic login under User administration / Users / User data.
The default settings for the administrator are
User: Administrator
Password: Admin or admin
Confirm the entry with "Apply". Then press "Log out" in the top right-hand corner
2.Enter a new login to the system with the user (e.g. FTCUser1) without a password.
3.The password for FTCUser1 is set during the logout process: Log out and enter the password.
4.The function is now active
Note: After the user logs out, the dialogue for assigning a new password is always displayed.
Control via the console (cmd):
plink -v -batch -ssh -2 -4 -C -N -P 22 -l {user} -pw {password} -L {localPort}:{localIp}:{remotePort} {remoteIp}
The {...} must be replaced by your own data.
Example:
plink -v -batch -ssh -2 -4 -C -N -P 22 -l FTCUser1 -pw Eisbaer -L 1100:192.168.178.123:1100 192.168.178.234
Note:
If the following error message appears, SSH transmission is not possible. In this case, the function must be enabled via Putty.
Connection abandoned.
Cannot confirm a host key in batch mode
FATAL ERROR: Cannot confirm a host key in batch mode
Further test via the browser:
http://127.0.0.1:1100/GET_DEV_STATUS
If there is a connection (driver is on), an output will appear in the browser (e.g. 1=1).