Assa Abloy FT-Connect

<< Click to Display Table of Contents >>

Navigation:  Components > Manufacturer specific drivers >

Assa Abloy FT-Connect

This driver can be used to integrate the FT-Connect security and access control system.

 

 

Data points of the component

Component name

Type

Type Function

Dynamic

Folder

Contains the data points created under "Channels".

Diagnosis [Text]

Output

Error texts are output here. These can be displayed using the"Log window" component, for example. Attention: Diagnostic or debug outputs are only intended for errors. Please only use them after consulting the support team! If used, they can significantly impair the performance of the service

Extended diagnostics

Input

(De)Activates the extended debug output. Attention: Diagnostic or debug outputs are only intended for use in the event of an error. Please only use them after consulting the support team! If used, they can significantly impair the performance of the service

Messages [Text]

Output

Output of communication messages in text form.

Driver On/Off

Bidirectional

(De)activation of the component at service start.

Connection status

Output

If there is a connection to the device, an On signal is output. If the connection is interrupted, an Off signal is output (after the set time-out time).

 

 

Properties of the component

Component name

Standard

Standard Function

Connection

 

Connection settings to the gateway with IP and login data. Only FTCUser1 or FTCUser2 can be used as the user.

There are 2 IP ports, which are preset to 1100.

The port (remote) is used for access from the EisBaer to the Assa Abloy FT-Connect (outgoing connection).

The port (local) is used for the connection from the Assa Abloy FT-Connect to the EisBaer (incoming connection).

Depending on the network, the firewall rules may need to be adjusted.
The TSB controller must be accessible in order to import the SSH host key.

Channels

0

The devices are imported from the server and displayed in the channel list. The names must be unique.

Update pause [s]

5

Pause time between 2 system queries.

Driver On/Off

 

(De)Activation of the component at service start.

 

Access only works with FTCUsers

A password must be set for these. To do this, the FT-Manager is called up with a web browser via the IP address. (Factory setting: https:\\1.1.1.1)

 

1.To activate the corresponding function (extended view), switch off automatic login under User administration / Users / User data.

The default settings for the administrator are

User: Administrator

Password: Admin or admin

Confirm the entry with "Apply". Then press "Log out" in the top right-hand corner

2.Enter a new login to the system with the user (e.g. FTCUser1) without a password.

3.The password for FTCUser1 is set during the logout process: Log out and enter the password.

4.The function is now active

 

Note: After the user logs out, the dialogue for assigning a new password is always displayed.

 

Control via the console (cmd):

plink -v -batch -ssh -2 -4 -C -N -P 22 -l {user} -pw {password} -L {localPort}:{localIp}:{remotePort} {remoteIp}

 

The {...} must be replaced by your own data.

 

Example:

plink -v -batch -ssh -2 -4 -C -N -P 22 -l FTCUser1 -pw Eisbaer -L 1100:192.168.178.123:1100 192.168.178.234

 

Note:

If the following error message appears, SSH transmission is not possible. In this case, the function must be enabled via Putty.

Connection abandoned.

Cannot confirm a host key in batch mode

FATAL ERROR: Cannot confirm a host key in batch mode

 

Further test via the browser:

http://127.0.0.1:1100/GET_DEV_STATUS

If there is a connection (driver is on), an output will appear in the browser (e.g. 1=1).