This driver is used to connect to the intelligent battery storage units from Commeo.

 

Data points of the component

Name

Type

Function

Operating error (flags)

Output

Output of the operating flag as a numerical value (see manufacturer's table)

Diagnosis [Text]

Output

Error texts are output here. These can be displayed e.g. with the component"protocol window". Attention: Diagnostic or debug outputs are only intended for use in the event of an error. Please only use them in consultation with the support team! If used, these can considerably impair the performance of the service.

Extended diagnosis

Input

(De)Activates the extended debug output. Caution: Diagnostic or debug outputs are only intended for use in the event of an error. Please use only after consultation with the support team! If used, they can significantly affect the performance of the service.

Information (Flags)

Output

Output of the information flag as a numerical value (see manufacturer's table)

Critical errors (flags)

Output

Output of the error flag as a numerical value (see manufacturer's table)

State of charge

Output

The SoC (State of Charge) value gives the current available system capacity as a percentage of the maximum capacity when the system is fully charged.

Power

Output

Power indicates the current actual value of the power flow into or out of the system. Positive power is defined as charging power, negative power is defined as discharging power.

Maximum charging current

Output

The maximum charge current is equal to the SoP charge divided by the system voltage.

Relay

Bidirectional

Opening and closing of the relay.

Relay status

Output

0 - Relay locked (standby)

1 - Relay unlocked and switched off (standby)

2 - Relay unlocked and switched on (on)

3 - Block error

4 - Hardware error

5 - Pre-charge active

6 - Pre-charge error

7 - ON error (error detected but relay not confirmed as OFF)

SoP Discharge

Output

Maximum power available for discharging

SoP Charging

Output

Maximum available power for charging

Voltage

Output

The voltage value indicates the system voltage and the current value indicates the system current as a result of the configuration of the system. Positive values are defined as charging current, negative values as discharging current from the battery's point of view.

Current

Output

The voltage value indicates the system voltage and the current value indicates the system current as a result of the configuration of the system. Positive values are defined as charging current, negative values as discharging current from the battery's point of view.

System status

Output

1 - Idle

2 - Configuring

3 - Charging

4 - Discharging

5 - Error

Temperature (Avg)

Output

Average temperature of all blocks in °C with one decimal place.

Temperature (Max)

Output

Maximum block temperature value in the system in °C with one decimal place.

Temperature (Min)

Output

Minimum block temperature value in the system in °C with one decimal place.

Driver On/Off

Bidirectional

(De)activate the component at service start.

Connection status

Output

If there is a connection to the unit, an on signal is output. If the connection is interrupted, an off signal is output (after the set time-out time).

Warnings (Flags)

Output

Output of the warning flag as a numerical value (see manufacturer's table).

 

 

Properties of the component

Name

Standard

Function

IP Address

 

The IP address of the Commeo ccuHV is entered here. Communication is established via port 504.

Driver On/Off

 

(De)activates the component.