DMX

<< Click to Display Table of Contents >>

Navigation:  Components > Driver >

DMX

The DMX driver is an invisible server component with the possibility of controlling 512 DMX addresses/channels.

The channels are coded at the DMX fixtures. There are 512 inputs on the component for controlling the DMX addresses.

A maximum of 32 units (better less) can be connected per DMX line. The terminating resistor (DMX terminator) of 120 Ohm is important.

 

Data points of the component

Name

Type

Function

Diagnosis [Text]

Output

Attention: Diagnostic or debug outputs are only intended for error cases. Please use only with consultation with the support team! If used, these can significantly affect the performance of the service.

Channels

Folder

The 512 data points are made available in the Channels folder. The communication direction can be set in the channel editor.

Connection status

Output

If the connection to the DMX gateway is successful, an on signal is output.

Driver On/Off

Bidirectional

Driver On or Off.

 

 

Properties of the component

Name

Default

Function

Channels

512

Here the channels can be edited interms of name and direction of communication (to gateway, from gateway and both directions).

Driver Type

ArtNet

Indicates which DMX protocol is used. Currently only the Artnet protocol is supported.

IP Address (Gateway)

255.255.255.255

Here the IP address of the DMX gateway is set. The broadcast address is preset. This is used to address all gateways in the network.

UDP Port [No.]

6454

Here the communication port of the DMX gateway is set.

DMX Universe [No.]

0

Here the number of the desired DMX universe (V3 or V4) is set.

Cyclic transmission

 

Sends in a defined time interval.

Transmission interval [ms]

1000

Set the time interval for sending.

Send delay [ms]

 

If the number is greater than 0, the time in milliseconds is waited before a command is sent. In the meantime, other channels can be changed.

Activate receiver

 

Caution: Only one DMX component may have its receiver activated.

Local IP address

 

For receiving DMX messages, the local IP address must be set here.

Driver On/Off

 

Switch driver on or off.

 

For the connection via Ethernet a "DMX Over Ethernet" interface is needed, which supports the "ArtNet" protocol. We recommend the "DMX Over Ethernet" interfaces of the company Enttec, which can be obtained from us.

 

Model: ODE (External Power Supply)

Model: ODE with PoE (Power over Ethernet)

 

Note: To configure the "DMX Over Ethernet" interface, the company provides Enttec, a free tool (Node Management Utility) for download on the website. You should always use the latest version here.

 

Note: The Remote Device Management or RDM protocol is not implemented. Therefore, state information can not be received from DMX bus devices.