Honeywell MB-Secure [x2500]

<< Click to Display Table of Contents >>

Navigation:  Components > Manufacturer specific drivers >

Honeywell MB-Secure [x2500]

This is an invisible driver component, which is designed for the Honeywell MB-Secure. Depending on the MB-Secure license, different data points can be used. Honeywell distinguishes 3 license levels:

#1: Area states and events Detector group states and events Macro control.

#2: Area states and events Detector group states and events Detector/input states and events Macro control Outputs directly controllable

#3: Area states and events Detector group states and events Detector/input states and events Macro control Outputs directly controllable Event streaming ZK information (user etc.)

 

Global Data points

Name

Type

Function

Request all states

Input

An arbitrary signal is used to start a query of all status messages.

Request all states (running)

Output

If a query is active, a true signal is output.

Request all states (last duration [ms])

Output

Output of the last query duration.

Debug [Text]

Output

Error texts are output here. These may e.g. with the "Log window" component. Attention: Diagnostics or debug outputs are only intended for the case of an error. Please use only after consultation with the support team! These may significantly affect the performance of the service when used

Verbose Debug

Input

(De) Activate extended debug output. Attention: Diagnostics or debug outputs are only intended for the case of an error. Please use only after consultation with the support team! These may significantly affect the performance of the service when used

Dynamic

Folder

Contains folders for scopes, devices, and macros. All data points may vary depending on the device.

Debug Events

Input

When activated, additional event outputs are displayed.

System

Folder

Output of system information.

- Description

Output

Display of the device description.

- Serial

Output

Output of the version of the serial number from the bridge.

- Version (Bootloader)

Output

Output of the version of the boot loader.

- Version (Executable)

Output

Output of the version of the application.

Driver On/Off

Bidirectional

(De) Activate the component

Driver State

Output

Boolean output from driver status.

Cyclic state requests

Bidirectional

(De) Activates the cyclic status query

 

Properties of the component

Name

Standard

Function

IP-Address

 

Enter the IP address of the Honeywell.

Port

443

Setting for the communication port.

User/Client

 

Specification of the user name / client name

Password

 

Input for the password

Connection check interval [s]

30

Time interval to check the connection.

Channels

0

Opens the channel editor

Cyclic state requests

x

(De) Activates the cyclic status query

Status request intervall [s]

60

Setting for the polling interval in seconds.

Driver On/Off

 

(De) Activate the component