<< Click to Display Table of Contents >> Navigation: Components > Manufacturer specific drivers > Lutron [x200] |
If this component is created, it counts as 200 components.
Properties
Name |
|
function |
|---|---|---|
Devices |
0 |
Opens the editor for creating the devices. This is not a complete device, but for the sake of flexibility, individual components (A device usually consists of several components) configured. Each component must have a (unique) name, the Lutron Integration ID of the associated device, the component number, and the type of component. At the moment, only key-panel components are supported. |
Connection |
Telnet... |
Setting the Lutron connection. At the moment, only Telnet is supported. |
Driver On/Off |
|
This can be used to set whether the component should be active when the system is started. |
Data points of the component
Name |
Type |
function |
Update |
Input |
Triggers a new query. |
Debug |
Output |
General debug. The diagnostic information is displayed there, linked to the [Signal] input of the log window. |
Debug - Sent Messages |
Output |
The diagnostic information is displayed there, linked to the [Signal] input of the log window. |
Dynamic |
Folder |
In the folder "Dynamic", a sub-folder is created for each component defined in the channels. |
- Device (Type Panel-Button) |
|
|
-- Button pressed/released |
Bidirectional |
Pressing "switch / released" displays the current status according to the messages received, provided that this is a Pressed / Released message. In addition, a Pressed and Released message can be sent here (depending on the Boolean value sent to the component via the SP). |
-- Button hold/released |
Bidirectional |
"Hold / Release switch" displays the current status according to the messages received, provided it is a Hold / Hold Released message. In addition, a Hold and Hold-Released message can be sent over this (depending on the Boolean value sent to the component via the SP). |
-- Button Multi Tap |
Bidirectional |
The "Multi-operation switch" displays the current status according to the messages received, provided that it is a multitap message. In addition, a multitap message can be sent if a true is sent via the SP to the component. |
- Device (Type Panel-LED) |
|
|
-- Led on/off |
Bidirectional |
"LED on / off" displays the current status of the LED according to the received messages, provided it is an LED message. The SP is set to true if the LED status is set to 1 (on), 2 (flash), or 3 (fast flash). In addition, the associated LED can be switched on / off (status 0 or 1). |
-- Led flash |
Bidirectional |
"LED blink" displays the current status of the LED according to the received messages, provided that this is an LED message. The SP will be true if the LED status 2 (flash) is set, otherwise the SP will be set to false. In addition, the associated LED can be set to the flashing mode (status 2). |
-- Led flash (rapid) |
Bidirectional |
"LED flashing (fast)" displays the current status of the LED according to the received messages, as long as it is an LED message. The SP is set true if the LED status 3 (fast flash) is set, otherwise the SP is set to false. In addition, the associated LED can be set to fast-blink mode (status 3). |
Driver On/Off |
Bidirectional |
Activate component at runtime |
Connection state |
Output |
Returns the driver state. |