OCPP charge station data

<< Click to Display Table of Contents >>

Navigation:  Components > E-Mobility >

OCPP charge station data

With this invisible server component, linked data points of a charging station can be duplicated with DLM. The assignment of another station is defined via the station name.

 

Data points of the component

Name

Type

Function

Enabled

Output

Output whether the charging station is active or not.

Connection number

Bidirectional

Number of the charging point of the wallbox

Authorisation - active

Bidirectional

(De)activate authorisation

Authorisation - last accepted ID tag

Output

Output of the user ID that was last accepted.

Authorisation - last rejected ID tag

Output

Output of the user ID that was last rejected.

Authorisation - last accepted ID tag

Output

Output of the user ID that was last accepted.

Backend defined

Output

If information on the backend is missing, an off signal is output, otherwise an on signal.

Backend connected

Output

If the backend is connected, an ON signal is output.

Command - (de)activate charging point

Input

With an ON signal, the charging point is activated and can be used.

Command - Start transaction

Input

Starts the charging process

Command - Stop transaction

Input

Stops the loading process

Command - Open interlock

Input

Opens the charging socket lock.

Preferred charging point

Output

Due to 1 single-phase charging, some charging points can be marked as "Preferred" (true at this output). This provides a more symmetrical load due to the phase rotation of L1, L2 and L3.

Diagnosis [Text]

Output

Error texts are output here. These can be displayed e.g. with the component"protocol window". Attention: Diagnostic or debug outputs are only intended for use in the event of an error. Please only use them in consultation with the support team! If used, these can considerably impair the performance of the service.

Query effective charging profile

Input

The active charging profile is output as text at the diagnostic output.

Transfer energy (since reset)

Output

Output of the transferred energy since the last reset of the counter reading.

Energy transmitted (total)

Bidirectional

Output of the total transmitted energy

Transmit energy (transaction)

Output

Output of the transmitted energy in the current transaction

Reset energy

Input

Resets the energy counter to 0.

Extended diagnosis

Input

The diagnostic output is extended via an on signal at this input. Attention: Diagnostic or debug outputs are only intended for use in the event of an error. Please use only after consultation with the support team! If used, they can considerably impair the performance of the service.

Error - Number

Output

Error output as number 0-15. Meaning see below.

Error - Text

Output

Output of the error code: 0=ConnectorLockFailure, 1=EVCommunicationError, 2=GroundFailure, 3=HighTemperature, 4=InternalError, 5=LocalListConflict, 6=NoError, 7=OtherError, 8=OverCurrentFailure, 9=OverVoltage, 10=PowerMeterFailure, 11=PowerSwitchFailure, 12=ReaderFailure, 13=ResetFailure, 14=UnderVoltage and 15=WeakSignal.

In use (OCPP)

Output

If the charging station has connected to the OCPP backend, an on signal is output.

If DC Station

Output

If the charging station is a DC charging station, an on signal is output here.

Calendar editor

Bidirectional

Data point for the calendar

Charging power (requested)

Bidirectional

Setting for the desired charging power for the vehicle.

Charging power plot [filename]

Output

Output for the plotter file name

Charging power plot [URL]

Output

Output of the url for display in an image component.

Charging point data (OCPP - local backend)

Bidirectional

Data point for communication with the OCPP component

Charging current (set)

Bidirectional

Possibility to set the charging current in [A]

Measured value - state of charge

Output

Outputs the state of charge in %, if available.

Measured value - power (grid)

Output

Outputs the measured power of the charging station in [W].

Measured value - power (car)

Output

Outputs the measured power of the vehicle in [W].

Measured value - voltage (total vehicle)

Output

Outputs the measured voltage of the vehicle in [V]

Measured value - voltage (L1-N)

Output

Outputs the measured voltage in [V]

Measured value - voltage (L2-N)

Output

Outputs the measured voltage in [V]

Measured value - voltage (L3-N)

Output

Outputs the measured voltage in [V]

Measured value - current (total vehicle)

Output

Outputs the measured current in [A]

Measured value - current (L1)

Output

Outputs the measured current in [A]

Measured value - current (L2)

Output

Outputs the measured current in [A]

Measured value - current (L3)

Output

Outputs the measured current in [A]

Measured value - current (phase maximum)

Output

Output of the highest measured current of all phases

Phase used (L1)

Output

If this phase is used, an ON signal is output. Otherwise an OFF signal.

Phase used (L2)

Output

If this phase is used, an ON signal is output. Otherwise an OFF signal.

Phase used (L3)

Output

If this phase is used, an ON signal is output. Otherwise an OFF signal.

Delete profiles

Input

Use any command to delete the profile data for the charging station.

Serial number

Output

Outputs the serial number of the wallbox

Station - On/Off

Bidirectional

(De)activates the charging station

Station - FW Version

Output

Firmware version of the charging station

Station - ID

Bidirectional

ID of the charging station

Station - Connected

Output

Indicates whether the charging station is connected to a vehicle (on) or not (off).

Station - Restart

Input

The charging station is restarted with an on edge.

Station name

Bidirectional

Name of the charging station

Status - Charging

Output

Charging station is in charging mode (on) or not (off)

Status - Number

Output

Status number:

0 = preparing

1 = finished

2 = available

3 = charging

4 = faulted / unavailable

5 = suspended

Status Number (OCPP)

Output

0 = available

1 = preparing

2 = charging

3 = suspended by EVSE

4 = suspended by EV

5 = finished

6 = reserved

7 = unavailable

8 = faulted

Status - Text

Output

Status output (see status number)

Status - Available

Output

If the station is available, an on signal is output.

Driver On/Off

Bidirectional

(De)activating the component

 

Properties of the component

Name

Default

Function

Station name

t.b.d

Name of the charging station, which must match the name in the OCPP.

Connection number

1

Number of the charging point of the wallbox

Driver On/Off

 

Defines whether the driver is automatically activated at the start of the project.