<< Click to Display Table of Contents >> Navigation: Components > Manufacturer specific drivers > ABB Sigma i-Bus |
A connection to the SIGMA i-Bus Modular can be established with the aid of the "SIB connection" component. The component is unvisible, d. H. the operator does not see this component in the client.
Data points of the component
Name |
Type |
function |
|---|---|---|
Release All Outputs |
Input |
Triggers the release of all outputs. |
Release All Groups |
Input |
Triggers the release of all groups (01-99) |
Outputs |
Folder |
Output 001 - 252; Status is output or switching command sent to output. |
Update Outputs |
Input |
Triggers the update of the groups. |
Block Outputs |
Folder |
Output blocking 001 - 252; Blocking status of the output is output. |
Release Outputs |
Folder |
Output Enable 001 - 252; Output is released. |
Debug |
Output |
Diagnosis output for error analysis. Can be output to a value-dependent text or the log window. The diagnostic information is displayed there, linked to the [Signal] input of the log window. |
Inputs |
Folder |
Input 001 - 252; Status is output or switching command sent to input. |
Update Inputs |
Input |
Triggers the update of the inputs. |
Groups |
Folder |
Group 01 - 99; Status is output or switching command sent to group. |
Update Groups |
Input |
Triggers the update of the groups. |
Block groups |
Folder |
Block group 01 - 99; Blocking status of the group is output. |
Group release |
Folder |
Group Release 01 - 99; Group is released. |
Monitor |
Folder |
Monitor 001 - 252; Status of monitor address is output. |
Driver On/Off |
Bidirectional |
Driver status indicator and driver on or off. |
Connection State |
Output |
Displays the status of the SIB driver. |
Set Time |
Input |
This object can be used to set the time of the SIGMA i-Bus control panel. |
Properties
Name |
Standard |
function |
|---|---|---|
COM-Port |
|
This parameter defines the COM interface to which the SIGMA i-Bus central unit is connected. |
Driver On/Off |
|
Enables the SIB driver. |
Normal Write Delay [ms] |
100 |
Standard write delay |
Write Delay 1 [ms] |
100 |
Write delay for the 1. repetition |
Write Delay 2 [ms] |
100 |
Write delay for the 2. repetition |
Write Delay 3 [ms] |
100 |
Write delay for the 3. repetition |
Write Delay 4 [ms] |
100 |
Write delay for the 4. repetition |
Write Delay 5 [ms] |
100 |
Write delay for the 5. repetition |