SNMP Trap-Agent

<< Click to Display Table of Contents >>

Navigation:  Components > Driver > SNMP >

SNMP Trap-Agent

This component allows asynchronous SNMP traps to be sent to SNMP trap receivers.

 

Fixed is a trap with the following information:

•EisBaerversion (0)

•Solution (1)

•Project (2)

 

The object ID of the trap is 1.3.6.1.4.1.44301.1. The 3 variables also have an Object ID. The basic object ID (Enterprise OID) is 1.3.6.1.4.1.44301 (reserved for Alexander Maier GmbH). Attached is a 1 (for the EisBaer information) and the number, which is given after each information. The trap number is fixed as 1 (only relevant for V1 traps).

e.g. 1.3.6.1.4.1.44301.1.2 -> project name

In addition, the project engineer can define further traps (with freely selectable object IDs).

 

Properties

Name

 

function

Enterprise OID

1.3.6.1.4.1.44301

Here you can enter the Enterprise-Object ID. This is used for all traps when trap version 1 is set.

Channels

0

Custom traps can be created here. The specification of the trap number is only relevant if SNMP is set to version 1. Furthermore, the trap-specific object ID and the data type of the trap value can be defined. There are the types: Bool, Double, Int32, UInt32 and String available.

Heartbeat interval [s]

60

Here you can define the interval in which the standard trap (version, solution, project) is sent.

Local IP

 

Here, the IP address of the local network interface to be used is entered.

Agent Port

161

Here you enter the local port to be used by the agent component.

Manager IP

 

The IP address of the computer to which the traps are to be sent is specified here. The IP address must be specified.

Manager Port

162

This specifies the port associated with the remote SNMP trap recipient.

SNMP Trap Version

one

Opens the editor for setting the trap version. If V3 is used, the authentication and encryption passwords and the associated protocols can be specified.

V2 Module Identity

 

Opens the editor for setting the agent identity (only relevant for trap version 2 or 3)

Driver On/Off

 

This can be used to set whether the component should be active when the system is started.

 

 

Shared-Properties

Name

Type

function

Debug [Text]

Output

Error messages are displayed here. The diagnostic information is displayed there, linked to the [Signal] input of the log window.

Driver On/Off

Bidirectional

Switch the driver on/off.

Dynamic

Folder

Contains the data points of the created channels

Channel001

Input

Here, the associated value inputs are created for each defined trap. If a value is sent to the component via one of these SPs, a corresponding trap with the received value is generated as content and sent to the defined trap receiver.

 

 

 

Driver Datapoints

The data point window displays all SPs and the corresponding object ID and trap number.